Map Recent Data Charts Control Radar Alarms Notes Maintenance Contact

To carry out maintenance, use the Android app.

This page is for reading and downloading what has already been recorded. The visit itself is done on a phone at the site, offline, and uploaded on the trip or afterwards (depending on cell service).

Download the app

‹ all sites

Gordon 3

2026-09-05 20:39

Group
CoG
Site
Gordon 3
Data file
Gordon_3.csv
Started
2026-09-05 20:39:13
Ended
2026-09-05 20:44:34
Times
phone local time UTC-04:00
Rows
73

Photographs (4)

Gordon_3_20260905_2039_dtec_204024.jpg
Gordon_3_20260905_2039_dtec_204024.jpg
Gordon_3_20260905_2039_radar_204235.jpg
Gordon_3_20260905_2039_radar_204235.jpg
Gordon_3_20260905_2039_turb_204255.jpg
Gordon_3_20260905_2039_turb_204255.jpg
Gordon_3_20260905_2039_wide_203920.jpg
Gordon_3_20260905_2039_wide_203920.jpg

The record

TimeEventItemValueUnit PointStandardNote
20:39:13 visit started Gordon 3 CoG
20:39:13 method chosen DTEC — depth mrcm
20:39:13 job added by hand DTEC — depth not in this site's data
20:39:13 method chosen DTEC — EC clean
20:39:13 job added by hand DTEC — EC not in this site's data
20:39:13 method chosen DTEC — temperature mrcm
20:39:13 job added by hand DTEC — temperature not in this site's data
20:39:13 method chosen Radar — depth distance
20:39:13 method chosen Turbidity — NTU ccc
20:39:13 job added by hand Turbidity — NTU not in this site's data
20:39:13 method chosen Battery maintenance swap
20:39:14 site check Radar — no rainfall ok
20:39:14 site check Access — safe and stable ok
20:39:15 site check No damage in work area ok
20:39:20 photograph, wide photos/Gordon_3_20260905_2039_wide_203920.jpg 43.5366 -80.2553 gps
20:40:24 photograph, sensor photos/Gordon_3_20260905_2039_dtec_204024.jpg 43.5364 -80.2553 gps
20:40:54 depth-pressure step Manual depth invert to water surface 220 mm 1 220 before the clean
20:41:11 depth-pressure step Sensor-reported depth at that moment 260 mm 1 220 before the clean
20:41:15 depth-pressure step Probe removed from water done 1
20:41:16 depth-pressure step Probe body cleaned done 1
20:41:17 depth-pressure step Probe returned to water at the same height done 1
20:41:54 taken out of order DTEC — depth left unfinished skipped manual depth after replacing
20:41:54 depth-pressure step Sensor-reported depth after replacing 26 mm 1 after the clean
20:42:00 ec step Cell rinsed with DI water done
20:42:00 ec step Electrodes wiped done
20:42:01 ec step Cell remounted done
20:42:04 temp step Reference thermometer 55 °C 1 55 before the clean
20:42:08 temp step Sensor temperature 22 °C 1 55 before the clean
20:42:10 temp step Probe lifted out of the water done 1
20:42:11 temp step Probe body and bead wiped done 1
20:42:12 temp step Probe returned to the same depth done 1
20:42:16 temp step Reference thermometer (after) 22 °C 1 22 after the clean
20:42:19 temp step Sensor temperature (after) 22 °C 1 22 after the clean
20:42:35 photograph, sensor photos/Gordon_3_20260905_2039_radar_204235.jpg 43.5363 -80.2553 gps
20:42:37 depth-radar step Distance mount face to water surface 2222 mm 1 2222
20:42:40 depth-radar step Radar angle from horizontal 79 ° 1
20:42:43 depth-radar step Sensor-reported distance at that moment 2225 mm 1 2222
20:42:46 depth-radar step Mount and bracket secure done 1
20:42:55 photograph, sensor photos/Gordon_3_20260905_2039_turb_204255.jpg no gps
20:43:06 turbidity precln Reading 1 · LED ON 10 NTU 1 10
20:43:08 turbidity precln Reading 1 · LED OFF 1 NTU 1 10
20:43:10 taken out of order Reading 2 · LED ON at point 1 before the clean skipped the ten second wait between readings
20:43:11 turbidity precln Reading 2 · LED ON 10 NTU 1 10
20:43:13 turbidity precln Reading 2 · LED OFF 1 NTU 1 10
20:43:14 di rinse transfer rinsed and moved to point 2 done 1 before the clean
20:43:19 turbidity precln Reading 1 · LED ON 100 NTU 2 100
20:43:21 turbidity precln Reading 1 · LED OFF 2 NTU 2 100
20:43:23 taken out of order Reading 2 · LED ON at point 2 before the clean skipped the ten second wait between readings
20:43:24 turbidity precln Reading 2 · LED ON 100 NTU 2 100
20:43:27 turbidity precln Reading 2 · LED OFF 2 NTU 2 100
20:43:30 turbidity cleaned sensor cleaned done the second pass begins here
20:43:33 turbidity postcln Reading 1 · LED ON 10 NTU 1 10
20:43:35 turbidity postcln Reading 1 · LED OFF 1 NTU 1 10
20:43:36 taken out of order Reading 2 · LED ON at point 1 after the clean skipped the ten second wait between readings
20:43:38 turbidity postcln Reading 2 · LED ON 10 NTU 1 10
20:43:38 turbidity drift LED ON after minus before 0 NTU 1 10
20:43:40 turbidity postcln Reading 2 · LED OFF 1 NTU 1 10
20:43:40 turbidity drift LED OFF after minus before 0 NTU 1 10
20:43:41 di rinse transfer rinsed and moved to point 2 done 1 after the clean
20:43:44 turbidity postcln Reading 1 · LED ON 100 NTU 2 100
20:43:46 turbidity postcln Reading 1 · LED OFF 1 NTU 2 100
20:43:47 taken out of order Reading 2 · LED ON at point 2 after the clean skipped the ten second wait between readings
20:43:48 turbidity postcln Reading 2 · LED ON 100 NTU 2 100
20:43:48 turbidity drift LED ON after minus before 0 NTU 2 100
20:43:50 turbidity postcln Reading 2 · LED OFF 1 NTU 2 100
20:43:50 turbidity drift LED OFF after minus before -1 NTU 2 100
20:43:52 turbidity remounted sensor rinsed and returned to its mount done
20:43:56 battery step Batteries changed done
20:43:56 batteries changed battery pack changed
20:44:19 final check battery 3606 mV fail
20:44:19 final check last logged 1 min ago pass
20:44:33 taken out of order ending the visit skipped the final check did not pass; closing close-ups for 3 probes; the closing wide shot
20:44:34 visit ended Gordon 3